MECAVENT acoustic louvres

The acoustic louvre, also known as an acoustic slat, acoustic grille, or louver, allows air to pass through while reducing noise escaping from openings: machine rooms, technical rooms, and noisy industrial areas. MECAVENT SA’s PERS acoustic louvres combine blades filled with absorbent material with weather protection, providing an overall attenuation of 10 to 18 dB(A) depending on the depth.

The PERS range at a glance:

  • 4 depths: 200, 300, 400, and 600 mm
  • Overall attenuation of 10 to 18 dB(A)
  • Standard dimensions from 200 × 350 mm to 2,500 × 2,500 mm, other dimensions on request
  • Raw or RAL powder-coated galvanized steel, stainless steel, or aluminum on request

A louvre sized for your project

Louvre attenuation is calculated by MECAVENT for each project, taking into account the airflow in the louvre section, the required sound pressure level at the defined point, and the sound power of the source. Send us your project data: we will provide a complete selection calculation, including pressure drop and the resulting sound pressure level.

The PERS range: 4 depths, 4 attenuation levels

ModelDepthOverall attenuationWeight
PERS 200200 mm10 dB(A)33 to 46 kg/m²
PERS 300300 mm13 dB(A)43 to 58 kg/m²
PERS 400400 mm15 dB(A)78 to 90 kg/m²
PERS 600600 mm18 dB(A)86 to 116 kg/m²

Overall attenuation on a reference spectrum. Standard widths from 200 to 2,500 mm, heights from 350 to 2,500 mm; any other dimension on request.

Construction and finishes

PERS acoustic louvres are made of galvanized steel sheet, raw or powder-coated in any RAL color (RAL 9010 as standard). Versions in stainless steel, aluminum, or other materials are available on request. The blades are filled with absorbent material protected by a perforated sheet; their inclination also allows for mounting at the end of a duct, either directly or with a frame.

Options and accessories

  • Insect or bird screen
  • Rear filter with frame (PERS-F100), replaceable media
  • Insulation adapter from 30 to 500 mm and wall brackets
  • Control damper
  • Back-to-back mounting
  • Side-by-side coupling for large openings

Applications

Air intakes and exhausts for machine rooms and technical rooms, workshops, and noisy industrial areas, complementing an acoustic enclosure or a silencer to treat noise from an industrial ventilation installation.

Frequently Asked Questions

What is the difference between an acoustic louvre, slat, and grille?

These are three names for the same product: a frame equipped with absorbent blades that allows air to pass through while reducing noise. The term “louvre” is also commonly used.

Which depth should I choose?

It depends on the required attenuation and the allowable pressure drop: from 10 dB(A) for the PERS 200 to 18 dB(A) for the PERS 600. We perform the selection calculation for each project.

What information is needed for a quote?

Opening dimensions, airflow, sound power of the source, required noise level and distance from the measurement point, mounting type, and desired finish. Louvres are delivered approximately 30 mm smaller than the opening to facilitate installation.